Option – ModBus

The ModBus option module has been specifically designed for use with the DHC-100 Positioner via plug and socket installation. This module provides an isolated RS-485 bus connection using the ModBus protocol.

Resources

Ideal Applications Include:

Specifications

Bus Connection:

Type: ANSI TIA/EIA RS-485 (electrically isolated up to 1500 Vrms)
Protocol: ModBus (selectable RTU or ASCII mode)
Logic “1”: +VBA
Logic “0”: -VBA
Selectable Address: 0-255 (1 to 247 usable)
Selectable line terminating resistor (RBA): 150 ohm
Line Polarization: Not required

Environmental:

Operating Temperature Range: 0C to 60C
Storage Temperature Range: -40C to 85C
Relative Humidity Range: 0 to 90% (noncondensing)

Cable Characteristic Impedance:

A value of 100 ohms or greater may be preferred, especially for 19.2K and higher baud rates

Transmitter Output:

Differential Output Voltage (VBA):

  • 5V Max @ No load
  • 1.5V min @ 54 ohm load

Output short circuit current:

  • A to B: 95mA typical
  • A or B to COM: 113mA typical

Transmitter Input:

Input Impedance (RBA): 96K ohms min (1/8 node)
Input Logic Threshold Voltage (VBA): 30mV min, 200 mV max
Input Hysteresis: 20mV Typical